Recommended initialization
Resets most settings and the history data.
1: Select parameter 14-22 Operation Mode.
2: Press [OK].
3: Select [2] initialization.
4: Press [OK].
5: Disconnect the mains supply and wait until the display turns off.
6: Reconnect the mains supply. The frequency converter is now reset.
Manual initialization
Resets ALL settings and the history data
1: Disconnect from mains and wait until the display turns off.
2:
2a: Press [Status] - [Main Menu] - [OK] at the same time while powering up the LCP 102, graphical display.
2b: Press [Menu] - [OK] while powering upt he LCP 101, numerical display.
3: Release the keys after 5 s.
4: The frequency converter is now programmed according to default settings.