Skip to Content
VLT® AutomationDrive EZ FC 321Enable speed limit over 50/60Hz

VLT® AutomationDrive EZ FC 321

Here, you'll find support for your VLT® AutomationDrive EZ FC 321

Enable speed limit over 50/60Hz

Select to show motor speed variables and parameters using output frequency (Hz).

  • 0-02 Motor Speed Unit [1] Hz

Enter the analog input scaling value that corresponds to the maximum reference feedback value

  • 6-15 Terminal 53 High Ref.

  • 6-25 Terminal 54 High Ref.

Enter the maximum reference. The maximum reference is the highest value obtainable by summing all references

  • 3-03 Maximum Reference

Enter the maximum limit for motor speed in Hz. The output frequency must not exceed 10% of the switching frequency

  • 4-14 Motor Speed High Limit Hz

Enter the maximum limit on the output frequency. This is a final limit for all configurations.

  • 4-19 Max Output Frequency.

Need more help?

Ask a different questionVLT® AutomationDrive EZ FC 321
Select a different product
Sitemap
Privacy policyTerms of useCookies